Published20/01/2025
-
Deadline24/02/2025
-
Opening of tenders24/02/2025
-
Today20/03/2025
Utilities
- indicates text translated automatically in your browsing language
Stephanus Primary School ; Heat supply systems Text automatically translated in your browsing language Automatically translated
In the basement, an R32 heat pump cascade (about 100 kW each thermally) is installed and supplied with environmental energy by a ready-to-use well system. Heating is carried out via underfloor heating distributors with heating circuits, which allow a switch to free cooling in summer. The existing sports hall is connected to the static heating circuit distributor via a local heat pipe, with ball valves at the end of the technical room. The hot water for the kitchen is supplied decentrally via residential stations with an electric reheating function. The heating registers of the four AHUs on the roof are connected to the heating system. Text automatically translated in your browsing language Automatically translated
http://www.deutsche-evergabe.de/dashboards/dashboard_off/c3f60ad7-90e4-42c8-9080-01335c82d6a7
http://www.deutsche-evergabe.de/dashboards/dashboard_off/c3f60ad7-90e4-42c8-9080-01335c82d6a7
This content published on this page is meant purely as an additional service and has no legal effect. The Union's institutions do not assume any liability for its contents. The official versions of the relevant tendering notices are those published in the Supplement of Official Journal of the European Union and available in TED. Those official texts are directly accessible through the links embedded in this page. For more information please see Public Procurement Explainability and Liability notice.